R410A Series
NRF(E), RT(E) is dedicated to R410A series thermal expansion valve is an integrated expansion valve, suitable for air conditioning, commercial refrigeration, transportation, air conditioning and refrigeration and other fields.
contact us- Technical Parameters
- Accessories
- Download
Characteristics
- Suitable refrigerant: R410A
- Maximum working pressure: 45bar
- Evaporation temperature range : - 40°C - +15°C
- Static superheat adjustment range: 1K-8K
- Maximum opening superheat: 8K
- MOP (Motor Overload Protection) function is available with a maximum protection pressure of 170psi.
General
NRF(E), RT(E) is dedicated to R410A series thermal expansion valve is an integrated expansion valve, suitable for air conditioning, commercial refrigeration, transportation, air conditioning and refrigeration and other fields.
Superheat regulation
The factory setting of static superheat is 4K, and the adjustable range is 1K-8K. Adjustment method: Unscrew the bottom sealing nut, turn the adjusting rod one turn clockwise (close the small), increase the static superheat by 1.5K, turn the adjustment rod one turn counterclockwise (open large) and decrease the static superheat by 1.5K.
Pressure balance type: After the model, the letter "E" is in the form of external balance, and the letter "E" is not in the form of internal balance.